8 Object Dictionary
44
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
60FD (Hex) - Digital Inputs
This object contains the drive digital output status (seen as input to the network).
The content of this object is equal to drive MEMOBUS/Modbus register 004A (Hex) (drive output terminal status
monitor U1-11) and depends on the drive the option is used with. For details on the content of this register, refer to the
technical manual for the drive.
Bit definitions:
0-15 = Reserved (Set to zero)
16-31 = MEMOBUS/Modbus register: 0x004A, U1-11 (Output terminal status)
60FE (Hex) - Digital Outputs
This object is used to set drive digital inputs (seen as output from the network).
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
60FD
0
Drive digital input status
Read Only
Tx
0...(2
32
-1)
Bit No. (Hex)
Function
Description
0 to F
Reserved
–
10 to 1F
Bit 0 to F of drive register 004A (Hex) (drive output terminal status
monitor U1-11)
1: ON
0: OFF
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
60FE
–
Drive digital input command
Read/Write
–
–
0
Number of elements
Read Only
–
0...255
1
Physical outputs
Read/Write
Rx/Tx
0...(2
32
-1)
Bit No. (Hex)
Function
Description
0 to 17
Reserved (Set to zero)
–
18
Terminal S3 Function
MEMOBUS/Modbus register:
0x0001#0x0040 (1 = set, 0 = clear)
19
Terminal S4 Function
MEMOBUS/Modbus register:
0x0001#0x0080 (1 = set, 0 = clear)
20
Terminal S5 Function
MEMOBUS/Modbus register:
0x0001#0x0100 (1 = set, 0 = clear)
21
Terminal S6 Function
MEMOBUS/Modbus register:
0x0001#0x0200 (1 = set, 0 = clear)
22
Terminal S7 Function
MEMOBUS/Modbus register:
0x0001#0x0400 (1 = set, 0 = clear)
23
Terminal S8 Function
MEMOBUS/Modbus register:
0x0001#0x0800 (1 = set, 0 = clear)
24
External Fault (EF0)
MEMOBUS/Modbus register:
0x0001#0x0004 (1 = set, 0 = clear)
25
Fault Reset
MEMOBUS/Modbus register:
0x0001#0x0008 (1 = set, 0 = clear)
26 to 31
Reserved (Set to zero)
–