6 DSP301 and DSP402 Specifications
20
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
DSP402 State Machine
The CANopen DSP402 specification indicates the state machine of the drive. Since the DSP402 adapter is external to the
inverter, the whole state machine must be implemented in the option card itself.
CANopen DSP402 Controlword/Statusword
This section describes how to control the drive via Controlword/Statusword and how to access drive parameters.
Table 6 Controlword
Table 7 Statusword
Controlword Operation Mode Specific Bits in Velocity Mode
Table 8 Controlword Operation Mode Specific Bits in Velocity Mode
Bit Number
Controlword
Application Reference/CPI Function Calls
0
Switch on
This bit controls the DS402 state machine - See
Table 10
1
Enable voltage
This bit controls the DS402 state machine - See
Table 10
2
Quick stop
This bit controls the DS402 state machine - See
Table 10
3
Enable operation
This bit controls the DS402 state machine - See
Table 10
4
Operation mode specific
Please see
Table 8
for more details
5
Operation mode specific
Please see
Table 8
for more details
6
Operation mode specific
Please see
Table 8
for more details
7
Fault reset
This bit controls the DS402 state machine - See
Table 10
8
Halt
Not implemented
9
Operation mode specific
Please see
Table 8
for more details
10
Manufacturer specific
NA
11
Manufacturer specific
NA
12
Manufacturer specific
NA
13
Manufacturer specific
NA
14
Manufacturer specific
NA
15
Manufacturer specific
NA
Bit Number
Statusword
Drive Reference
0
Ready to switch on
This bit controls the DS402 state machine - See
Table 11
1
Switched on
This bit controls the DS402 state machine - See
Table 11
2
Operation enabled
This bit controls the DS402 state machine - See
Table 11
3
Fault
This bit controls the DS402 state machine - See
Table 11
4
Voltage enabled
1: High voltage is applied to the drive
5
Quick stop
This bit controls the DS402 state machine - See
Table 11
6
Switch on disabled
This bit controls the DS402 state machine - See
Table 11
7
Warning
1: During alarm condition
8
Manufacturer specific
NA
9
Remote
1: Controls the frequency reference or the run command from the option
0: Does not control the frequency reference or the run command from the option
10
Target reached (Op mode spec)
See
Table 9
11
Internal limit active
0: Always, not implemented
12
Operation mode specific
Refer to
Table 9
for more details
13
Operation mode specific
Refer to
Table 9
for more details
14
Manufacturer specific
NA
15
Manufacturer specific
NA
Bit Number
Controlword
Drive Reference
4
rfg enable
0: Does not control the frequency reference from the option
1: Controls the frequency reference from the option
5
rfg unlock
0: Discards any new NET set-point
1: Uses new NET set-point
6
rfg use ref
0: Forces NET set-point to zero
1: Uses NET set-point
9
Not implemented
Not implemented