8 Object Dictionary
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
43
604C (Hex) - vl Dimension Factor
The vl dimension factor is multiplied with the target velocity. The quotient of the subindexes vl dimension factor
numerator and vl dimension factor denominator determines the vl dimension factor.
Default Value = 1
This parameter affects other objects such as:
• 0x6042 vl_target_velocity
• 0x6043 vl_velocity_demand
• 0x6044 vl_velocity_actual_value
• 0x6046 vl_velocity_min_max_amount
• 0x6048 vl_velocity_acceleration
• 0x6049 vl_velocity_deceleration
• 0x604A vl_velocity_quick_stop
and is always used in a product.
604D (Hex) - vl Pole Number
The vl pole number sets the number of motor poles and is used to calculate all speed related values in r/min. This value
corresponds to the number of motor poles setting in the drive.
MEMOBUS/Modbus register: 0x0311, E2-04 (Number of motor poles)
6060 (Hex) - Modes of Operation
This object sets the mode of the device. The object supports 2 (Velocity Mode) only.
Value: 2: Velocity mode
6061 (Hex) - Modes of Operation Display
This object shows the mode of the device. The object supports 2 (Velocity Mode) only.
Value: 2: Velocity mode
Value: -2: Vendor specific mode
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
604C
1
vl dimension factor numerator
Read/Write
Rx/Tx
-2
31
...(2
31
-1)
Internal in EtherCAT option card, save in NVS memory.
Default Value = 1
2
vl dimension factor denominator
Read/Write
Rx/Tx
-2
31
...(2
31
-1)
Internal in EtherCAT option card, save in NVS memory.
Default Value = 1
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
604D
0
vl pole number
Read/Write
Tx
0...255
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
6060
0
Modes of operation
Read/Write
Rx/Tx
-128...127
Index (Hex)
Subindex
Content
Access
PDO Mapping
Value Range
6061
0
Modes of operation display
Read Only
Tx
-128...127