12 Fault Diagnosis and Possible Solutions
58
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
Option Error Management
This section describes the errors managed by the option and the linked actions taken.
Table 24 Option Error Management
Option Error
Description
Error Indication
Possible Solution
OP
→
SAFEOP/PREOP
when drive running
When an EtherCAT state transition from
OP
→
SAFEOP/PREOP was made when
the drive was in OPERATION enabled.
bUS Error is triggered in drive.
Note:
Error against drive will be
cleared when the next lower to
higher EtherCAT state transition
is made.
Check and correct state machine
transitions in Controlword.
OP
→
SAFEOP
EtherCAT WD time out
If the EtherCAT watchdog time out is
enabled (Default in ESI file) and output
data from PLC to the drive is not updated
in time, an error will be triggered.
bUS Error is triggered in drive.
Note:
Error against drive will be
cleared when the next lower to
higher EtherCAT state transition
is made.
• Check network connection (e.g. if
cables plugged in at each node).
• Check telegram timing. Are
telegrams sent to the slave the error
occurred on?
OP
→
SAFEOP
1. Drive frame check
sequence error
2. Drive COMID error
1. Drive has detected a Sum check error.
2. Drive has detected a Communication
Option ID error.
Possible cause:
1. Option card is overloaded.
2. Option is not properly processing the
state.
1. Drive fault: oF
32
2. Drive fault: oF
30
• Disable process data OUT sync
manager channel.
• Force EtherCAT state change to
SAFEOP.
OP
→
SAFEOP
1. Option card frame check
sequence error
2. Option card COMID error
1. Option card has detected a Sum check
error.
2. Option card has detected a
Communication Option card ID error.
Possible cause:
1. Drive system is overloaded.
2. Drive is not properly processing the
state.
1. Drive fault: oF
32
2. Drive fault: oF
30
• Disable process data IN sync
manager channel.
• Force EtherCAT state change to
SAFEOP.
Initial power-up sequence not
completed within 10 seconds.
Possible cause:
Drive is not processing the internal
interface protocol.
Drive does not support EtherCAT option
card.
Drive fault: oF
00
Option will log FATAL event
record in NVS memory and set
ERR LED: solid RED, see
Table 4
.
• Check drive firmware version.
• If drive firmware version is correct,
replace option card.
• Replace the drive.
I/F proc time out
Option card has not processed any drive
system frames in 1000 ms.
Possible cause:
Drive has stopped serving the internal
interface to option card or HW failure.
Option will log FATAL event
record in NVS memory, and set
ERR LED: solid RED, see
Table 4
.
Force EtherCAT state to INIT.
Option ID Error: Power-up
sequence copyright string
mismatch.
Drive reported invalid copyright string in
power-up process.
Option will log FATAL event
record in NVS memory, and set
ERR LED: solid RED, see
Table 4
.
Replace option card.