7 Operation
7.3.2 Setting the Overtravel Limit Function
7-10
(4) Servomotor Stop Mode for P-OT and N-OT Input Signals
Set the following parameters to specify the servomotor Stop Mode when P-OT and N-OT input signals are used.
Specify the servomotor Stop Mode when either of the following signals is input during servomotor operation.
• Forward run prohibited input (P-OT, CN1-7)
• Reverse run prohibited input (N-OT, CN1-8)
The torque limit is specified as a percentage of rated torque.
Stopby dynamic
brake
Coast to a stop
Decelerate to a
stop
Zero clamp
Coast status
Coast
status
Pn001.1
setting
Stop Mode
After stopping
Pn001.1 = 1 or 2
Pn001.0 = 0, 1
Pn001.1 = 0
0
1
2
Pn001.0 = 2
Overtravel
Stop by dynamic
Brake
Parameter
Description
Pn001
n.
0
Stops the servomotor the same way as changing to Servo OFF (according to Pn001.0).
n.
1
Decelerates the servomotor to a stop at the preset torque value or less, and then locks the
servomotor in Zero Clamp Mode.
Torque setting: Pn406 emergency stop torque
n.
2
Decelerates the servomotor to a stop at the preset torque value or less, and puts the
servomotor in coast status.
Torque setting: Pn406 emergency stop torque
Pn406 specifies the stop torque applied for overtravel when the input signal for prohibiting forward or reverse rotation is
used.
Pn406
Emergency Stop Torque
Setting Range
Setting Unit
Factory Setting
Setting Validation
0 to 800%
1%
800%
Immediately
Max. torque setting for an
emergency stop
Forward run
prohibited input
P-OT (CN1-7)
Reverse run
prohibited input
N-OT (CN1-8)
Stop Mode
Pn406
Stop by dynamic brake
Coast to a stop
Decelerate to a stop
Содержание SGDS Sigma III Series
Страница 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Страница 21: ......
Страница 29: ...1 Outline 1 8 2 Connecting to SGMSH SGMGH Servomotors Power Supply Three phase 200VAC SGMGH Servomotor...
Страница 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Страница 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Страница 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Страница 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Страница 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...
Страница 375: ...Sigma II User s Manual Index Index 8...