6 MECHATROLINK II Communications
6.3.20 Release Latch Mode (LTMOD_OFF: 29H)
6-26
6.3.20 Release Latch Mode (LTMOD_OFF: 29H)
Byte
LTMOD_OFF
Description
Command
Response
1
29H
29H
Processing
classifications
Control com-
mand group
Synchronization
classifications
Asynchronous
2
ALARM
Processing time
Within communi-
cations cycle
Subcommand
Can be used
3
STATUS
• Releases the modal latch mode.
• Can be used during phases 2 and 3.
• During phase
1
Command warning 1(A.95A) will occur and the command
will be ignored.
• Check that CMDRDY is 1 to confirm that the Release Latch Mode command
has been received.
- It takes 500
µ
s max. for the Release Latch Mode command to start.
• Interference with another latch mode command
- During the execution of a command such as LATCH, ZRET, EX_POSING,
or SVCTRL, the LTMOD_ON command cannot be used. If this command is
used during the execution of these commands, the warning Command
warning 4 (A.95D) will occur.
4
5
MONITOR1
6
7
8
9
MONITOR2
10
11
12
13
SEL_MON 1/2
SEL_MON 1/2
14
IO_MON
15
16
WDT
RWDT
17
For
subcommands.
Refer to
6.4
Subcommands
.
For
subcommands.
Refer to
6.4
Subcommands
.
18
19
20
21
22
23
24
25
26
27
28
29
Содержание SGDS Sigma III Series
Страница 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Страница 21: ......
Страница 29: ...1 Outline 1 8 2 Connecting to SGMSH SGMGH Servomotors Power Supply Three phase 200VAC SGMGH Servomotor...
Страница 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Страница 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Страница 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Страница 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Страница 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...
Страница 375: ...Sigma II User s Manual Index Index 8...