6 MECHATROLINK II Communications
6.3.8 Start Synchronous Communications (SYNC_SET: 0DH)
6-14
6.3.8 Start Synchronous Communications (SYNC_SET: 0DH)
Byte
SYNC_SET
Description
Command
Response
1
0DH
0DH
Processing
classifications
Network com-
mand group
Synchronization
classifications
Asynchronous
2
ALARM
Processing time
Transmission
cycle or more
Subcommand
Cannot be used
3
STATUS
• Starts synchronous communications. Switches from phase 2 to phase 3.
• Processing is completed at the WDT changing edge.
However, if WDT errors are being masked by parameter Pn800.0, processing
is completed when this command is received.
• During phase 1, a MECHATROLINK II command warning1 (A.95A) will
occur and the command will be ignored.
• During phase 3, the command will be ignored (without a warning).
• The SERVOPACK will change to Servo OFF if this command is received.
• At the occurrence of the following alarms, this command must be transmitted
to restart synchronous communications.
- MECHATROLINK II Synchronization Error (A.E50)
- MECHATROLINK II Synchronization Failure (A.E51)
- MECHATROLINK II Communications Error (A.E60)
- MECHATROLINK II Transmission Cycle Error (A.E61)
4
5
6
7
8
9
10
11
12
13
14
15
16
WDT
RWDT
Содержание SGDS Sigma III Series
Страница 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Страница 21: ......
Страница 29: ...1 Outline 1 8 2 Connecting to SGMSH SGMGH Servomotors Power Supply Three phase 200VAC SGMGH Servomotor...
Страница 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Страница 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Страница 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Страница 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Страница 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...
Страница 375: ...Sigma II User s Manual Index Index 8...