Deployment I/O periphery
5.1 Overview
n
On this CPU the connectors for digital respectively analog signal and
Technological
functions
are combined in a one casing.
n
The project engineering happens in the Siemens SIMATIC Manager as CPU 314C-2
PN/DP from Siemens (314-6EH04-0AB0 V3.3). Here the CPU 013-CCF0R00 is para-
meterized via the
‘Properties’
dialog of the Siemens CPU 314C-2 PN/DP.
n
For parametrization of the digital I/O periphery and the
technological functions
the
corresponding sub modules of the CPU 314C-2 PN/DP is to be used.
n
The controlling of the operating modes of the
technological functions
happens by
means of handling blocks of the user program.
n
The integrated I/Os of the CPU may be used for
technological functions
or as
standard periphery.
n
Technological functions
and standard periphery may be used simultaneously with
appropriate hardware.
n
Read access to inputs used by
technological functions
is possible.
n
Write access to used outputs is not possible.
n
Chapter 5.3 ‘Analog input’ on page 91
–
2xUx12Bit (0 ... 10V)
–
The analog channels of the module are not isolated to the electronic power
supply.
–
The analog part has no status indication
n
Chapter 5.4 ‘Digital input’ on page 95
–
16xDC 24V
–
Interrupt functions parameterizable
–
Status indication via LEDs
n
Chapter 5.5 ‘Digital output’ on page 98
–
12xDC 24V, 0.5A
–
Status indication via LEDs
n
Chapter 5.6 ‘Counting’ on page 101
–
4 channels
–
Count once
–
Count continuously
–
Count Periodically
–
Chapter 5.6.4 ‘SFB 47 - COUNT - Counter con-
n
Chapter 5.7 ‘Frequency measurement’ on page 128
–
4 channels
–
Chapter 5.7.4 ‘SFB 48 - FREQUENC - Frequency
n
Chapter 5.8 ‘Pulse width modulation - PWM’ on page 137
–
2 channels
–
Chapter 5.8.4 ‘SFB 49 - PULSE - Pulse width
Project engineering and
parametrization
I/O periphery
Technological functions
VIPA System SLIO
Deployment I/O periphery
Overview
HB300 | CPU | 013-CCF0R00 | en | 16-40