Dependent on the mode of operation the LEDs show information about the state of oper-
ation of the PROFIBUS part according to the following pattern:
Master operation
DE
(Data Exchange)
BF
(Bus error)
Meaning
green
red
○
○
Master has no project, this means the interface is deactivated respectively
the master configured without slaves with no errors.
BB
○
CPU is in STOP state, the master is in "clear" state. All the slaves are in DE
and the outputs are of the slaves are disabled.
●
○
CPU is in STOP state, the master is in "operate" state. All the slaves are in
DE. The outputs are enabled.
●
BB
CPU is in RUN state, at least 1 slave is missing and at least 1 slave is in DE.
BB
BB
CPU is in STOP state, the master is in "clear" state. At least 1 slave is
missing and at least 1 slave is in DE.
○
●
PROFIBUS is interrupted (no communication possible)
○
BB
At least 1 slave is missing and no slave is in DE.
X
BB
At least 1 slave is not in DE.
on: ● | off: ○ | blinking (2Hz): BB
Slave operation
DE
(Data Exchange)
BF
(Bus error)
Meaning
green
red
○
○
Slave has no project.
○
●
There is a bus error.
BB
○
Slave is in state data exchange with master.
Slave CPU is in STOP state.
●
○
Slave is in state data exchange with master.
Slave CPU is in RUN state.
on: ● | off: ○ | blinking (2Hz): BB
LEDs PROFIBUS
VIPA System SLIO
Hardware description
Structure > LEDs