In the Siemens SIMATIC Manager the following steps should be executed:
1.
Start the Siemens hardware configurator with a new project.
2.
Insert a profile rail from the hardware catalog.
3.
Place at
‘Slot’
-Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
4.
Click at the sub module
‘PN-IO’
of the CPU.
5.
Select
‘Context menu
è
Insert PROFINET IO System’
.
6.
Create with [New] a new sub net and assign valid address data
7.
Click at the sub module
‘PN-IO’
of the CPU and open with
‘Context menu
è
Properties’
the properties dialog.
8.
Enter at
‘General’
a device name. The device name must be unique at the Ethernet
subnet.
Proceeding
VIPA System SLIO
Deployment CPU 013-CCF0R00
Hardware configuration - CPU
HB300 | CPU | 013-CCF0R00 | en | 16-40