So that you may the according Ethernet interface, you have to assign IP address parame-
ters by means of the "initialization".
Chapter 10.3 ‘TIA Portal - Hardware configuration -
Ethernet PG/OP channel’ on page 222
Please consider to use the same IP address data in your project for the CP 343-1.
1.
For the transfer, connect, if not already done, the appropriate Ethernet jack to your
Ethernet.
2.
Open your project with the Siemens TIA Portal.
3.
Click in the
Project tree
at
Online access
and choose here by a double-click your
network card, which is connected to the Ethernet PG/OP interface.
4.
Select in the
Project tree
your CPU and click at [Go online].
5.
Set the access path by selecting "PN/IE" as type of interface, your network card and
the according subnet. Then a net scan is established and the corresponding station
is listed.
6.
Establish with [Connect] a connection.
7.
Click to
‘Online
è
Download to device’
.
ð
The according block is compiled and by a request transferred to the target
device. Provided that no new hardware configuration is transferred to the CPU,
the entered Ethernet connection is permanently stored in the project as transfer
channel.
10.5.3
Transfer via memory card
The memory card serves as external storage medium. There may be stored several proj-
ects and sub-directories on a memory card. Please regard that your current project is
stored in the root directory and has one of the following file names:
n
S7PROG.WLD
n
AUTOLOAD.WLD
1.
Start the Siemens TIA Portal with your project.
2.
Create a wld file with
‘Project
è
Memory card file
è
New’
.
ð
The wld file is shown in the
Project tree
at "SIMATIC Card Reader" as "Memory
card file".
3.
Copy the blocks from the
Program blocks
to the wld file. Here the hardware configu-
ration data are automatically copied to the wld file as "System data".
4.
Copy the wld file at a suited memory card. Plug this into your CPU and start it
again.
ð
The transfer of the application program from the memory card into the CPU
takes place depending on the file name after an overall reset or PowerON.
S7PROG.WLD
is read from the memory card after overall reset.
AUTOLOAD.WLD
is read from the memory card after PowerON.
The blinking of the SD LED of the CPU marks the active transfer. Please regard
that your user memory serves for enough space for your user program, other-
wise your user program is not completely loaded and the SF LED gets on.
Initialization
Transfer
Proceeding
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Project transfer > Transfer via memory card
HB300 | CPU | 013-CCF0R00 | en | 16-40