1.
Insert another station and configure a CPU.
2.
Designate the station as "...DP master".
3.
Add your modules according to the real hardware assembly.
4.
Open the properties dialog of the DP interface of the CPU by means of a double-
click at
‘MPI/DP’
.
5.
Set Interface: type to "PROFIBUS".
6.
Connect to PROFIBUS and preset an address (e.g. 2) and confirm with [OK].
7.
Switch at Operating mode to "DP master" and confirm the dialog with [OK].
8.
Connect your slave system to this master system by dragging the "CPU 31x" from
the hardware catalog at
Configured stations
onto the master system and select your
slave system to be coupled.
9.
Open the
Configuration
at
Object properties
of your slave system.
10.
Via double click to the according configuration line you assign the according input
address area on the master CPU to the slave output data and the output address
area to the slave input data.
11.
Save, compile and transfer your project to your CPU.
Project engineering of the
master section
VIPA System SLIO
Option: PROFIBUS communication
Deployment as PROFIBUS DP slave