By means of a screwdriver there is the possibility to remove the connectors e.g. for
module exchange with a fix wiring. For this each connector has a release lever centrally
on its top side. Unlocking takes place by the following proceeding:
1.
Remove connector:
Push your screwdriver horizontally into the slot between connector and release
lever, until it stops.
2.
Push the screwdriver down:
ð
The connector is unlocked and can be removed by turning downwards.
CAUTION!
Via wrong operation such as pressing, the screwdriver upward
the release lever may be damaged.
3.
Plug connector:
The connector is plugged by setting it at the bottom line and engage with a with a
slight twist upwards into the release lever.
(1) DC 24V for electronic section supply of the CPU, the internal I/Os and SLIO bus
(2) DC 24V for power section supply integrated I/Os
(3) DC 24V for power section supply SLIO bus
The electronic power section supply is internally protected against higher
voltage by fuse. The fuse is located inside the CPU and can not be
changed by the user.
Remove connectors
(module replacement)
Standard wiring
VIPA System SLIO
Basics and mounting
Wiring > Wiring CPU 01xC
HB300 | CPU | 013-CCF0R00 | en | 16-40
21