Operating parameters
Description
Assignment
Comparison value
The count value is compared with the
comparison value
.
See also the parameter "Characteristics of the output":
n
No main counting direction
–
Range of values: -2)
31
to +2)
31
-1
n
Main counting direction forward
–
Range of values: -2
31
to end value-1
n
Main counting direction backward
–
Range of values: 1 to +2
31
-1
0
Hysteresis
The
hysteresis
serves the avoidance of many toggle pro-
cesses of the output, if the counter value is in the range of
the
comparison value
.
0, 1:
Hysteresis
disabled
Range of values: 0 to 255
0
Input
Description
Assignment
Signal evaluation
Specify the signal of the connected encoder:
n
Pulse/direction At the input count and direction signal
are connected
n
At the input there is an encoder connected with the fol-
lowing evaluation:
–
Rotary encoder single
–
Rotary encoder double
–
Rotary encoder quadruple
Pulse/direction
Hardware gate
Gate control exclusively via channel 3:
n
enabled: The gate control for channel 3 happens via
SW and HW gate
n
disabled: The gate control for channel 3 exclusively
happens via SW gate
Chapter 5.6.7.2 ‘Gate function’ on page 122
disabled
Count direction inverted
Invert the input signal
‘Direction’
:
n
enabled: The input signal is inverted
n
disabled: The input signal is not inverted
disabled
VIPA System SLIO
Deployment I/O periphery
Counting > Parametrization
HB300 | CPU | 013-CCF0R00 | en | 16-40
112