The following parameters may be accessed by means of the properties dialog of the VIPA
CPU.
n
Function X3
–
MPI/DP (default): In this operating mode parameters are active, which you set on
sub module
‘MPI/DP’
of the Siemens CPU 314C-2 PN/DP.
PROFIBUS communication’ on page 186
–
PTP: With this operating mode the RS485 interface acts as an interface for serial
point-to-point communication. Here data may be exchanged between two stations
Chapter 6 ‘Deployment PtP communication’
n
Additional retentive memory
–
Here enter the number of retentive memory bytes. With 0 the value
‘Retentive memory
è
Number of memory bytes starting with MB0’
is set, which is
pre-set at the parameters of the Siemens CPU.
–
Range of values: 0 (default) ... 8192
n
Additional retentive timer
–
Enter the number of S7 timers. With 0 the value
‘Retentive memory
è
Number S7 timers starting with T0’
is set, which is pre-set at the parameters of
the Siemens CPU.
–
Range of values: 0 (default) ... 512
n
Additional retentive counter
–
Enter the number of S7 counter. With 0 the value
‘Retentive memory
è
Number S7 counters starting with C0’
is set, which is pre-set at the parameters
of the Siemens CPU.
–
Range of values: 0 (default) ... 512
n
Diagnostics interrupt (default: deactivated)
–
Error: 5L+ (DC 24V DI power section supply)
–
Error: 2L+ (DC 24V DO power section supply)
–
Error: 3L+ (DC 24V SLIO bus power section supply)
–
Short circuit / overload: DO
–
Short circuit / overload: Sensor
VIPA specific parameters
VIPA System SLIO
Deployment CPU 013-CCF0R00
Setting VIPA specific CPU parameters
HB300 | CPU | 013-CCF0R00 | en | 16-40