5.6.2.2
Counter outputs
Pos.
Function
Type
Description
1
Sys DC 24V
I
1L+: DC 24V for electronic section supply
2
Sys 0V
I
1M: GND for electronic section supply
3
---
---
reserved
4
DC 24V
O
S+: DC 24V for sensor
5
0V
O
1M: GND for sensor
6
DO 0
O
+0.0: Digital output DO 0 / PWM 0 / Output channel counter 0
7
DO 1
O
+0.1: Digital output DO 1 / PWM 1 / Output channel counter 1
8
DO 2
O
+0.2: Digital output DO 2 / Output channel counter 2
9
DO 3
O
+0.3: Digital output DO 3 / Output channel counter 3
10
DO 4
O
+0.4: Digital output DO 4
11
DO 5
O
+0.5: Digital output DO 5
12
DO 6
O
+0.6: Digital output DO 6
13
DO 7
O
+0.7: Digital output DO 7
14
DO 8
O
+1.0: Digital output DO 8
15
DO 9
O
+1.1: Digital output DO 9
16
DO 10
O
+1.2: Digital output DO 10
17
DO 11
O
+1.3: Digital output DO 11
18
DC 24V
I
2L+: DC 24V for onboard DO power section supply
19
0 V
I
2M: GND for onboard DO power section supply / GND PWM
20
DC 24V
I
3L+: DC 24V for SLIO bus power section supply
21
0 V
I
3M: GND for SLIO bus power section supply
Every counter has an assigned output channel. For each counter you can specify the
behavior of the counter output via the parametrization with
‘Characteristics of the output’
and
‘Pulse duration’
‘Parameter overview’ on page 111