3.3 Technical data
Order no.
013-CCF0R00
Type
CPU 013C
Module ID
-
Technical data power supply
Power supply (rated value)
DC 24 V
Power supply (permitted range)
DC 20.4...28.8 V
Reverse polarity protection
ü
Current consumption (no-load operation)
120 mA
Current consumption (rated value)
360 mA
Inrush current
3 A
I²t
0.1 A²s
Max. current drain at backplane bus
1 A
Max. current drain load supply
6 A
Power loss
7 W
Technical data digital inputs
Number of inputs
16
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load voltage
ü
Current consumption from load voltage L+ (without load)
25 mA
Rated value
DC 24 V
Input voltage for signal "0"
DC 0...5 V
Input voltage for signal "1"
DC 15...28.8 V
Input voltage hysteresis
-
Frequency range
-
Input resistance
-
Input current for signal "1"
3 mA
Connection of Two-Wire-BEROs possible
ü
Max. permissible BERO quiescent current
0.5 mA
Input delay of "0" to "1"
3 µs – 15 ms / 0.5 ms – 15 ms
Input delay of "1" to "0"
3 µs – 15 ms / 0.5 ms – 15 ms
Number of simultaneously utilizable inputs horizontal con-
figuration
16
Number of simultaneously utilizable inputs vertical configu-
ration
16
Input characteristic curve
IEC 61131-2, type 1
VIPA System SLIO
Hardware description
Technical data
HB300 | CPU | 013-CCF0R00 | en | 16-40
47