37
WIKA operating instructions pneumatic high pressure controller, model CPC7000
0019104001D 10/2018 EN
EN
6.4.3.4
Rate Stability Parameters
Rate parameters for the control rate can be found in the Control Settings App and can be configured using the Rate Stable Window
and Rate Stable Delay buttons. The Rate Stable Window button allows the user to enter a value as a percentage of the active
range of transducer. This value represents the pressure window within which the control rate value would be considered stable by
the user. The Rate Stable Delay button lets the user add a desired delay until the control rate is considered stable while being in
the rate stable window.
Rate Stability
Parameters
Figure 6.4.3.4 Rate Stability Parameters
6.4.3.5
Vent Rate
The Vent Rate button in the Control Settings App lets the user to determine the rate at which pressure will vent in vent mode. By
default the rate of the vent is set similar to the control rate. Figure 6.4.3.5 displays the vent rate setting. The maximum allowable
rate of vent is 60 bar/second and the minimum vent rate is limited to 1 bar/second.
Figure 6.4.3.5 Vent Rate
6. Operation