Chapter 5 CANopen
Manual VIPA System 200V
5-106
HB97E - IM - Rev. 06/29
Electrical data
VIPA 253-2CA20
Power supply
DC 24V (20.4 ... 28.8) via front from ext. power supply
Current consumption at L+
max. 5A
Output current backplane bus
3.5A
Isolation
≥
AC 500V
Status indicator
by means of LEDs located on the front
Connectors/interfaces
9pin D-type (socket) CAN-Bus connection
CAN-Bus interface
Connection
9pin D-type plug
Network topology
Linear bus, active bus termination at one end, tap lines
permitted.
Medium
Screened three-core cable, unscreened cable permitted -
depending on environment.
Data transfer rate
10kBaud to 1MBaud
Max. overall length
1000m at 50kBaud without repeaters
Max. no. of stations
127 stations (depending on the master interface)
Output unit
Number of outputs
24
Nominal load voltage
DC 24V (20.4...28.8V) internal via CAN coupler
Output current per channel
1A (Total current max. 4A)
Status monitor
Power (PW) fuse ok, Error (ER) short circuit, overload
Programming data
Output data
3Byte
Dimensions and weight
Dimensions (WxHxD) in mm
50.8x76x78
Weight 150g
CANopen slave
IM 253CAN,
DO 24xDC 24V
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...