Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-71
With the
channel specific diagnostic
you gain detailed information about
the channel error within a module. For the usage of the
channel specific
diagnostic
you have to release the diagnostic alarm for every module via
the parameterization. The
channel specific diagnostic
can be activated via
the parameterization and has the following structure:
Channel-specific diagnostic
Byte
Bit 7 ... Bit 0
X
Bit 5 ... 0: ID number of the module that delivers the channel-
specific diagnostic (000001 ... 011111)*
z.B.: Slot 1 has ID no. 0
Slot 32 has ID no. 31
Bit 7, 6: 10 (fix) Code for channel-specific diagnostic
X+1
Bit 5 ... 0: Number of the channel or the channel group that
delivers the diagnostic (00000 .... 11111)
Bit 7 ... 6: 01=Input Module
10=Output
Module
11=In-/Output
Module
X+2
Bit 4 ... 0:
Error messages to Profibus standard
00001:
Short
circuit
00010: Undervoltage (Supply voltage)
00011: Overvoltage (Supply voltage)
00100: Output Module is overloaded
00101: Temperature rise output Module
00110: Open circuit sensors or actors
00111: Upper limit violation
01000: Lower limit violation
01001: Error - Load voltage at the output
- Sensor supply
- Hardware error in the Module
Error messages - manufacturer-specific
10000: Parameter assignment error
10001: Sensor or load voltage missing
10010:
Fuse
defect
10100:
Ground
fault
10101: Reference channel error
10110: Process interrupt lost
11001:
Safety-related
shutdown
11010:
External
fault
11010: Indefinable error - not specified
Bit 7 ... 5: Channel type
001:
Bit
010:
2
Bit
011:
4
Bit
100:
Byte
101:
Word
110:
2
Words
*)
Bit 5 ... 0: 000001...001000 (slot 1...8) at 253-1DP31 - ECO
The maximum number of
channel specific diagnostic
is limited by the total
length of 58Byte for diagnostic. By de-activating of other diagnostic ranges
you may release these areas for further
channel specific diagnostic
. For
each channel always 3 Byte are used.
Channel specific
Diagnostic
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...