Reset of the Ethernet coupler
Via [reboot node] a reset of the Ethernet coupler is initialized. After a re-
boot, you have to update the website via
home
.
By presetting a r
eset value
, you may additionally to the re-boot of the
Ethernet coupler delete the configuration or module parameters.
Permissible r
eset value
values are 1, 2 or 3. Other values are ignored!
Reset value= 1 Re-boot of the coupler (default setting)
Reset value= 2 Delete all module configurations (module names)
and re-boot the coupler
Reset value= 3 Delete all module parameters and re-boot the coupler
Reset value= 4 Reset password (Default-Value "00000000")
Resetting the password to its default value "00000000" is possible in a
special operation mode.
•
Power off the Ethernet coupler and pull it off from back plane bus.
•
Power up the Ethernet coupler again
•
Open the Web site of the Ethernet coupler by means of you Web
browser and the IP address.
•
Type in the default Password "00000000" at the parameter "reboot
node"
•
Set "Resetvalue =" 4 and click "reboot node".
→
Now the coupler resets
its password to default value "00000000" and boots up again.
Configure
Timeout
The coupler offers a connection timeout.
If the value 0 is transferred, this function is deactivated. (In the picture of
the Ethernet coupler "Timout: off" is shown).
Note!
Choose "Timout: off" if you want to control outputs via internet browser
otherwise all outputs are set to the secure state 0 after timeout.
With timeout values
>
0msec, an I/O connection must read/write faster
than the time value. If not, the connections are terminated and the outputs
are set to the secure state 0.
The RD LED blinks and the website shows "rdy" in small letters.
Confirm alarm
Using "confirm alarm", it is possible to clear a slots alarm status bit. By
setting a slot you need to set your couplers password and the slot (0 ... 31)
where the alarm status bit shall be confirmed. Then clicking the button
[confirm alarm] will clear the status bit and the "DiagAlarm" or "ProcAlarm"
message will disappear.
Reset password
Resetvalue =
dec
reboot node
1
Password =
Timeout =
msec
set timeout
0
Password =
Slot =
dec
confirm alarm
0
Password =
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...