Chapter 3 Profibus DP
Manual VIPA System 200V
3-52
HB97E - IM - Rev. 06/29
DP configurations error - entry
Length:
6
Depending on the mode and when the length of the configuration message
matches the length of the default configuration the different entries in the
configuration message are compared to the default configuration.
Byte
Bit 7 ... Bit 0
0
15h: DP configuration error - entry
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2
Configuration byte master (module identifier)
4
Configuration byte slave (module identifier)
3 Mode
0: Standard mode
1: 400-mode
Undervoltage/power failure
Length:
2
A time stamp is saved immediately to the EEPROM when a power failure
or a voltage drop is detected. If there is still enough voltage, the diagnostic
data is transferred to the master.
At the next restart, the time stamp in the EEPROM is used to generate an
undervoltage/power-off diagnostic message that is saved in the diagnostic
RAM.
Byte
Bit 7 ... Bit 0
0
1Eh: Undervoltage/power failure
V-bus configuration error
Length:
3
The configuration for the specified slot failed.
Byte
Bit 7 ... Bit 0
0
28h: V-bus configuration error
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
V-bus initialization error
Length:
2
General backplane bus error
Byte
Bit 7 ... Bit 0
0
29h: V-bus initialization error
V-bus bus error
Length: 2
Hardware error or module failure
Byte
Bit 7 ... Bit 0
0
2Ah: V-bus error
15h
1Eh
28h
29h
2Ah
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...