Manual VIPA System 200V
Chapter 6 DeviceNet
HB97E - IM - Rev. 06/29
6-21
LED
Description
PW on
The ER-LED blinks because the timer of the
ER blinks
I/O connection detected an error. The RD-LED blinks
RD blinks
because the I/O-connection does not exist any
BA on
longer. All inputs and outputs are set to zero.
The BA-LED is turned on because the connection with
the master is still established.
LED
Description
PW on
After POWER ON the PW-LED is turned on and
ER off
indicates that the power supply operates properly.
RD on
The RD-LED is turned on after a short delay since the
BA off
baudrate was transferred into the EEPROM.
LED
Description
PW on
The address that was set up on the coupler is not valid.
ER on
Change the address to a valid setting:
RD off
•
0...63 as DeviceNet address
BA off
•
90...92 for the definition of the baudrate
PW on
When the coupler is not connected to the DeviceNet,
ER on
an error was detected in the internal EEPROM or in
RD on
RAM. When a DeviceNet connection exists, it is also
BA on
possible that an error has occurred during the transfer
of the configuration data into the peripheral modules.
Note!
Errors that occur during POWER ON with DeviceNet
and master display the same combination of LEDs as
a hardware error.
It is possible to distinguish between these cases:
•
by interruption of the DeviceNet connection
→
ER-LED and RD are blinking!
•
with a network WHO in the
DeviceNet-Manager
→
in case of a hardware error the IM 253DN
will not appear on the network
Please call the VIPA hotline if a hardware error occurs!
Change of state
from operational
to connection
error status
Configuration
mode
POWER ON in
configuration
mode
Device error
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...