The module is equipped with four LEDs for diagnostic purposes. The
following table shows how the diagnostic LEDs are used along with the
respective colors.
Name
Color Description
PW
yellow Indicates that the supply voltage is available.
ER
red
On when an error was detected in the backplane bus communications.
RD
green Blinks at 1Hz when the self-test was positive and initialization was OK.
Is turned on when data is being communicated via the V-Bus.
BA
yellow Off the self-test was positive and the initialization was OK.
Blinks at 1Hz when the status is "Pre-operational".
Is turned on when the status is "Operational".
Blinks at 10Hz when the status is "Prepared".
Various combinations of the LEDs indicate the different operating states:
Components
LEDs
Status indicator as
a combination of
LEDs
PW on
Error during RAM or EEPROM initialization
ER on
RD on
BA on
PW on
Baudrate setting activated
ER blinks 1Hz
RD blinks 1Hz
BA blinks 1Hz
PW on
Error in the CAN baudrate setting
ER blinks 10Hz
RD blinks 10Hz
BA blinks 10Hz
PW on
Module-ID setting activated
ER off
RD blinks 1Hz
BA off
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...