Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-29
•
Create a new project System 300 and add a profile rail from the
hardware catalog.
•
Insert the CPU 315-2DP. Hardware catalog:
Simatic300
>
CPU-300
>
CPU315-2DP
(6ES7 315-2AF03-0AB0 V1.2)
•
Open the
Properties
of the
DP
part.
•
Choose at
Operating mode
"DP slave".
•
Set at
general
a Profibus DP slave address.
•
The data transfer areas are set at
configuration
. Please note only the
"MS" mode is supported.
•
Transfer as shown at "Transfer variants" above the system data to your
IM 208DP - not to the CPU! - and set the IM 208DP to RUN.
Note!
The parameters "Input" respectively "Output" at
configuration
always take
place from CPU sight.
"Input" refers to the input part and "Output" to the output part of the CPU.
The VIPA04D5.GSD is necessary for project engineering at a
superordinate master system.
•
Start your configuration program with a new project and configure the
superordinate Profibus master system.
•
Add a DP slave of the station type "CPU2xxDP". This is to find in the
hardware catalog at:
Profibus DP > Additional field devices > I/O > VIPA > VIPA_CPU2xxDP
after including VIPA04D5.GSD.
•
Assign the Profibus address to the DP slave that you’ve parameterized
at the slave.
•
For the Profibus communication, create the same I/O range that you’ve
parameterized at the slave in form of "modules". Please regard that a
slave output area relates to a master input area and vice versa.
•
Save your project and transfer it into the CPU of your master system.
Note!
If your DP master system is a System 200V module from VIPA, you may
parameterize the directly plugged-in modules by including a "DP200V"
slave system.
To enable the VIPA CPU to recognize the project as central system, you
have to assign the Profibus address 1 to your slave system!
Please take care at deployment of the IM 208 Profibus DP master that
this has a firmware version V 3.0 or higher; otherwise this may not be
used at a CPU 21x with a firmware version V 3.0 or higher. The
firmware versions are on a label at the backside of the modules.
Hardware-
configuration
IM 208DP
Hardware-
configuration
superordinate
master system
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...