Manual VIPA System 200V
Chapter 5 CANopen
HB97E - IM - Rev. 06/29
5-41
0 1
64
32
16
8
4
2
1
-
1
0
The address selector is used to specify the module-ID as well as the CAN
baudrate. Each module ID must be unique on the bus.
For details please refer to "IM 253CAN - CANopen slave - Baudrate and
module-" in this chapter.
Contrary to the coding switch described above the IM 253-1CA30 - ECO is
equipped by a DIL switch for addressing.
The CAN-bus coupler is equipped with an internal power supply. This
power supply requires DC 24V. In addition to the internal circuitry of the
bus coupler the supply voltage is also used to power any modules
connected to the backplane bus. Please note that the maximum current
that the integrated power supply can deliver to the backplane bus is 3.5A.
The back plane current of the IM 253-1CA30 - ECO is limited to 0.8A.
The power supply is protected against reverse polarity.
CAN-Bus and backplane bus are isolated from each other.
Attention!
Please ensure that the polarity is correct when connecting the power
supply!
Address selector
for Baudrate and
module-ID
Address selector
IM 253-1CA30 - ECO
Power supply
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...