Chapter 5 CANopen
Manual VIPA System 200V
5-68
HB97E - IM - Rev. 06/29
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x1011 0
Restore
parameters
Unsigned8
ro
N
0x01
Number of reset options
1
Restore
all
parameters
Unsigned32 rw
N
0x01
Resets all parameters
to their default values
By writing the string "load" in ASCII code (hex code: 0x64616F6C) into sub-
index 1, all parameters are set back to default values (delivery state)
at
next start-up (reset)
(byte sequence at the bus incl. SDO protocol: 0x23
0x11 0x10 0x01 0x6C 0x6F 0x61 0x64).
This activates the default identifiers for the PDOs.
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x1014 0
COB-ID
Emergency
Unsigned32 ro N
0x00000080
+
Node_ID
Identifier of the emergency
telegram
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x1016 0
Consumer
heartbeat time
Unsigned8
ro
N
0x05
Number of entries
1
Unsigned32 rw
N
0x00000000
Consumer heartbeat time
Structure of the "Consumer Heartbeat Time" entry:
Bits 31-24
23-16
15-0
Value Reserved
Node-ID
Heartbeat
time
Encoded as
Unsigned8
Unsigned8
Unsigned16
As soon as you try to configure a consumer heartbeat time unequal zero
for the same node-ID, the node interrupts the SDO download and throws
the error code 0604 0043hex.
Load default
values
Emergency
COB-ID
Consumer
heartbeat time
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...