Chapter 2
Installation planning and mounting
11
Mounting
Be sure to read the mounting and handling guidelines below before beginning to mount the controller.
Mounting and handling guidelines
Comply with the following guidelines:
•
Locate the host computer and the M3000 controller in areas secure from any disruption to data
communications or tampering.
•
Clean and clear all mounting areas of corrosive gases and airborne metallic particles. Avoid installing
near photocopiers due to contamination from toner particles.
•
Protect the M3000 from hazardous (high) voltages.
•
Mount the M3000 on a vertical surface with at least six inches (15.2 centimeters) clearance on all four
sides to support thermal air cooling.
•
Locate the M3000 in a place that provides a dedicated AC earth ground. The M3000 must be earth
grounded.
•
Keep interior and exterior housing of all M3000 enclosures and other components free of wire
remnants.
•
Avoid temperatures outside the range specified for the M3000 operating environment. Do not leave
boards or other components in direct sunlight.
•
To avoid mechanical damage, do not drop or stack boards.
•
Do not subject printed circuit boards to electrostatic discharge.
Mounting instructions
The enclosure can be mounted in one of two ways
•
Directly to the wall, or
•
Into a standard Electronics Industries Alliance (EIA), 19-inch open frame IT Rack.
Wall mounting
Mount the controller enclosure using the following steps and referring to Figure 1.
1. Remove the packing material from the enclosure.
2. Using the template provided, mark and drill four mounting holes.
3. Using customer furnished 1/4-in. (6 mm) threaded lag bolts or equivalent and washers, secure the
enclosure to the wall.
4. If required, install cable conduit to the M3000 enclosure knockout holes.
5. The enclosure has knockout holes on the sides, bottom, and back; the cable is pulled through these
holes. To open the holes, strike the knockouts from the outside of the enclosure.
CAUTION:
Do not apply power to any component during installation. Damage to components may occur if power
is incorrectly applied.
Содержание M3000
Страница 1: ...M3000 Installation Manual P N 460630001H 15JUNE11 ...
Страница 10: ...M3000 Installation Manual x ...
Страница 37: ...Chapter 3 Power Communications board 27 Host computer wiring Figure 9 Wiring host computer to first M3000 ...
Страница 39: ...Chapter 3 Power Communications board 29 Figure 11 Wiring modem to M3000 M 5 or serial printer ...
Страница 41: ...Chapter 3 Power Communications board 31 Figure 13 Wiring downstream away from the host using RS 232 ...
Страница 47: ...Chapter 4 PXNplus CPU board 37 Board layout Figure 16 PXNplus CPU board layout ...
Страница 58: ...M3000 Installation Manual 48 Board layout Figure 17 2RP reader board layout ...
Страница 65: ...Chapter 5 Reader processing boards 55 Figure 21 Wiring 2RP to Wiegand Strobed F 2F and supervised F 2F readers ...
Страница 68: ...M3000 Installation Manual 58 Figure 24 Wiring 2RP door strike external relay ...
Страница 72: ...M3000 Installation Manual 62 Board layout Figure 27 2SRP supervised reader board layout ...
Страница 78: ...M3000 Installation Manual 68 Figure 30 Wiring 2SRP to Wiegand F 2F Strobed and Supervised F 2F Readers ...
Страница 82: ...M3000 Installation Manual 72 Figure 19 Wiring 2SRP door alarm contact and exit request ...
Страница 84: ...M3000 Installation Manual 74 Figure 21 Wiring 2SRP door strike external relay ...
Страница 89: ...Chapter 5 Reader processing boards 79 Board layout Figure 24 8RP reader board layout ...
Страница 92: ...M3000 Installation Manual 82 Figure 26 Wiring 8RP to F 2F or Supervised F 2F Readers ...
Страница 94: ...M3000 Installation Manual 84 ...
Страница 97: ...Chapter 6 Optional DI and DO boards 87 Figure 31 20DI board layout ...
Страница 99: ...Chapter 6 Optional DI and DO boards 89 Figure 32 Wiring DI point ...
Страница 101: ...Chapter 6 Optional DI and DO boards 91 Figure 33 16DO board layout ...
Страница 102: ...M3000 Installation Manual 92 Figure 34 16DOR board layout ...
Страница 104: ...M3000 Installation Manual 94 Figure 36 Wiring output device to 16DOR board ...
Страница 152: ...M3000 Installation Manual 142 ...
Страница 156: ...M5 controller Installation Manual 146 Figure 76 Installing ferrite ...
Страница 160: ...M5 controller Installation Manual 150 ...
Страница 172: ...M3000 Installation Manual 162 ...