M3000
Installation Manual
100
6. If this computer is set for:
•
DHCP, then the
Obtain an IP address automatically
field is already selected. Select
Use the
following IP address
.
•
Static, write down the IP address and Subnet number. You will need to reset your computer back to
these numbers after the controller configuration is complete.
7. Enter the IP address
192.168.6.5
, or a similar valid IP address (
192.168.6.
x
where
x
is any
number between 1 and 254 except 6).
8. Change the subnet mask to
255.255.255.0
.
Note:
You do not need to change the gateway.
9. Click
OK
until all open windows are closed.
10. Connect the Cat-5 crossover cable from the Ethernet port on your laptop or computer directly to the
controller Ethernet port (no hub or switch).
11. If your controller is not yet powered up, do so now.
12. Open an Internet browser window on your computer.
13. In the browser’s Address field, enter the default static IP address of the controller:
192.168.6.6
14. When the Integrated Configuration Tool starts, enter your username and password.
Note:
The default values for username and password are
install
,
install
. We recommend that you
change these values for added security, as described on page 117.
Initial configuration: Windows XP
1. Click
Start
,
Control Panel
, then
Network Connections
.
2. Right-click on
Local Area Connection.
If the first option in the drop-down list box is:
•
Disable
, then the connection is enabled. Go to
step 3
.
•
Enable
, then select it to enable the connection. Return to
step 1
.
3. Select
Properties
from the drop-down list.
4. In the
This connection uses the following items:
section, select
Internet Protocol TCP/IP
.
5. Select
Properties
.
6. If this computer is set for:
•
DHCP, then the
Obtain an IP address automatically
field is already selected. Select
Use the
following IP address
.
•
Static, write down the IP address and Subnet number. You will need to reset your computer back to
these numbers once the controller configuration is complete.
7. Enter the IP address
192.168.6.5
, or a similar valid IP address (
192.168.6.
x
where
x
is any
number between 1 and 254 except 6).
8. Change the subnet to
255.255.255.0
.
Note:
You do not need to change the gateway.
9. Click
OK
until all open windows are closed.
Содержание M3000
Страница 1: ...M3000 Installation Manual P N 460630001H 15JUNE11 ...
Страница 10: ...M3000 Installation Manual x ...
Страница 37: ...Chapter 3 Power Communications board 27 Host computer wiring Figure 9 Wiring host computer to first M3000 ...
Страница 39: ...Chapter 3 Power Communications board 29 Figure 11 Wiring modem to M3000 M 5 or serial printer ...
Страница 41: ...Chapter 3 Power Communications board 31 Figure 13 Wiring downstream away from the host using RS 232 ...
Страница 47: ...Chapter 4 PXNplus CPU board 37 Board layout Figure 16 PXNplus CPU board layout ...
Страница 58: ...M3000 Installation Manual 48 Board layout Figure 17 2RP reader board layout ...
Страница 65: ...Chapter 5 Reader processing boards 55 Figure 21 Wiring 2RP to Wiegand Strobed F 2F and supervised F 2F readers ...
Страница 68: ...M3000 Installation Manual 58 Figure 24 Wiring 2RP door strike external relay ...
Страница 72: ...M3000 Installation Manual 62 Board layout Figure 27 2SRP supervised reader board layout ...
Страница 78: ...M3000 Installation Manual 68 Figure 30 Wiring 2SRP to Wiegand F 2F Strobed and Supervised F 2F Readers ...
Страница 82: ...M3000 Installation Manual 72 Figure 19 Wiring 2SRP door alarm contact and exit request ...
Страница 84: ...M3000 Installation Manual 74 Figure 21 Wiring 2SRP door strike external relay ...
Страница 89: ...Chapter 5 Reader processing boards 79 Board layout Figure 24 8RP reader board layout ...
Страница 92: ...M3000 Installation Manual 82 Figure 26 Wiring 8RP to F 2F or Supervised F 2F Readers ...
Страница 94: ...M3000 Installation Manual 84 ...
Страница 97: ...Chapter 6 Optional DI and DO boards 87 Figure 31 20DI board layout ...
Страница 99: ...Chapter 6 Optional DI and DO boards 89 Figure 32 Wiring DI point ...
Страница 101: ...Chapter 6 Optional DI and DO boards 91 Figure 33 16DO board layout ...
Страница 102: ...M3000 Installation Manual 92 Figure 34 16DOR board layout ...
Страница 104: ...M3000 Installation Manual 94 Figure 36 Wiring output device to 16DOR board ...
Страница 152: ...M3000 Installation Manual 142 ...
Страница 156: ...M5 controller Installation Manual 146 Figure 76 Installing ferrite ...
Страница 160: ...M5 controller Installation Manual 150 ...
Страница 172: ...M3000 Installation Manual 162 ...