RT-SVX24Q-EN
27
the atmosphere or merge with return main at
discharge side of steam trap.
☐
Position the steam trap discharge at least 12" below
the outlet connection on the coil.
☐
Use float and thermostatic traps in the system, as
required by the application.
O/A Pressure Sensor and Tubing
Installation (All VAV units and CV units
with return fan or StatiTrac)
☐
O/A pressure sensor mounted to the roof bracket.
☐
Factory supplied pneumatic tubing installed
between the O/A pressure sensor and the connector
on the vertical support.
☐
(Units with StatiTrac) Field supplied pneumatic
tubing connected to the proper fitting on the space
pressure transducer located in the filter section, and
the other end routed to a suitable sensing location
within the controlled space.
Evaporative Condenser
☐
Remove fan bracket.
☐
Hookup inlet and drain piping.
☐
Install heat tape if needed.
☐
Setup drain hold or drain on power loss.
☐
Setup Mechanical Float.
☐
Setup drain time.
☐
Setup water quality management (3rd party
system).
☐
Options setup.
☐
Calibrate Conductivity Controller.
☐
Setup blowdown setpoints on the conductivity
sensor.
Energy Recovery Wheel
☐
Verify that the wheel turns freely though a full
rotation.
☐
Confirm that all wheel segments are fully engaged
in the wheel frame and that the segment retainers
are completely fastened.
☐
Confirm the seal adjustment and proper belt
tracking on the wheel rim.