Figure 63.
Typical GBAS analog input wiring diagram for 90 to 162 ton CV and VAV control options
Table 44.
GBAS voltage vs. setpoint
Setpoint
GBAS 0-5 VDC
GBAS 0-10 VDC
Valid Range
Occ Zone Cooling Setpoint (CV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Unocc Zone Cooling Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Occ Zone Heating Setpoint (CV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F