108
RT-SVX24Q-EN
Table 46.
Service test guide for component operation — part I of II (continued)
Component
Being Tested
COMPONENT CONFIGURATION
Supply
Fan
Return
Fan
Exhaust
Fan
Condenser
Fans
Heat Stages
Compressor Stage
1
2
3
1
2
3
4
5
2A
OFF
OFF
OFF
1A-Off/1B-
Off/1C-Off/
1D-Off 2A-
On /2B-Off/
2C-Off & 2D-
Off
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
2B & 2C
OFF
OFF
OFF
1A-Off/1B-
On/1C-Off/
1D-Off 2A-
Off/2B-On/
2C-On/ 2D-
Off
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
2D
OFF
OFF
OFF
1A-Off/1B-
On/1C-Off
1D-Off 2A-
Off/2B-Off/
2C-Off/ 2D-
On
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
100, 118, 128, 140, 162 Ton — Evaporative Condensing
1A
OFF
OFF
OFF
1A 0 -100 %
2A OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
2A
OFF
OFF
OFF
1A OFF 2A 0
- 100%
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
SUPPLY FAN
ON
ON
OFF
ALL OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
RETURN FAN
ON
ON
N/A
ALL OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
EXHAUST FAN
OFF
N/A
ON
ALL OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N/A
GAS HEA
T
(Full Capacity)
ON
ON
OFF
ALL OFF
ON
ON
ON
OFF
OFF
OFF
OFF
N/A
STAGE 1
ON
ON
OFF
ALL OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
N/A
STAGE 2
ON
ON
OFF
ALL OFF
OFF
ON
N/A
OFF
OFF
OFF
OFF
N/A
Full Modulating
ON
ON
OFF
ALL OFF
10% - 90%
OFF
OFF
OFF
OFF
N/A
ELECTRIC HEAT
ON
ON
OFF
ALL OFF
ON
ON
ON
OFF
OFF
OFF
OFF
N/A
Stage 1
ON
ON
OFF
ALL OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
N/A
Stage 2
ON
ON
OFF
ALL OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
N/A
Stage 3
ON
ON
OFF
ALL OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
N/A
HYDRONIC HEAT
OFF
OFF
OFF
ALL OFF
100% Select
OFF
OFF
OFF
OFF
N/A
OUTSIDE AIR
DAMPERS
OFF
OFF
OFF
ALL OFF
100% Select
OFF
OFF
OFF
OFF
N/A
EXHAUST
DAMPERS
OFF
OFF
OFF
ALL OFF
100% Select
OFF
OFF
OFF
OFF
N/A
EVAP COND
N/A
Sump Pump
OFF
OFF
OFF
ALL OFF
100% Select
OFF
OFF
OFF
OFF
N/A
Sump Heater
OFF
OFF
OFF
ALL OFF
100% Select
OFF
OFF
OFF
OFF
N/A
Table 47.
Service test guide for component operation — part II of II
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Sump Pump
Sump
Heater
Econo
Damper
Exhaust
Damper
VFD Output
COMPRESSOR
90 - 105 Ton
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B
Closed
Closed
0%
Default
OFF
OFF
120 - 162 Ton
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B
Closed
Closed
0%
Default
OFF
OFF
CONDENSER FAN
S
90 - 105 Ton — Air Cooled