180
RT-SVX24Q-EN
Heat Stages 1 & 2 (On)
Turn the 115 volt control circuit switch 4S24 located
in the heater control panel to the On position.
Open the manual gas valve, located in the gas heat
section.
2. Once the configuration for the appropriate heating
system is complete, press the NEXT key until the
LCD displays the “Start test in __Sec.” screen. Press
the + key to designate the delay before the test is to
start. This service test will begin after the TEST
START key is pressed and the delay designated in
this step has elapsed. Press the ENTER key to
confirm this choice.
3. Press the TEST START key to start the test.
Remember that the delay designated in step 2 must
elapse before the system will begin to operate.
4. Once the system has started, check the appearance
of the flame through the sight glass provided on the
front of the heat exchanger. In appearance, a
normal flame has a clearly defined shape, and is
primarily (75%) blue in color with an orange tip.
5. Check the manifold gas pressure by using the
manifold pressure port on the gas valve. Refer to
for the required manifold pressure
for high-fire operation. If it needs adjusting, remove
the cap covering the high-fire adjustment screw on
the gas valve. Refer to
for the
adjustment screw location. Turn the screw
clockwise to increase the gas pressure or
counterclockwise to decrease the gas pressure.
6. Use a carbon dioxide analyzer and measure the
percentage of carbon dioxide in the flue gas. Refer
to the illustration in
. Take several
samples to assure that an accurate reading is
obtained. Refer to
for the proper
carbon dioxide levels. A carbon dioxide level
exceeding the listed range indicates incomplete
combustion due to inadequate air or excessive gas.
Combustion Air Adjustment (O
2
)
1. Use an oxygen analyzer and measure the
percentage of oxygen in the flue gas. Take several
samples to assure an accurate reading. Compare
the measured oxygen level to the combustion curve
in
. The oxygen content of the flue
gas should be 4% to 5%. If the oxygen level is
outside this range, adjust the combustion air
damper to increase or decrease the amount of air
entering the combustion chamber. Refer to
for the location of the combustion air
damper.
2. Recheck the oxygen and carbon dioxide levels after
each adjustment. After completing the high-fire
checkout and adjustment procedure, the low-fire
setting may require adjusting.
Low-Fire Adjustment (850 & 1100 MBH only)
1. Use the TEST initiation procedures outlined in the
previous section to operate the furnace in the low-
fire state (1st Stage).
2. Use a carbon dioxide analyzer and measure the
percentage of carbon dioxide in the flue gas. Refer
to the combustion curve in
, Inset
A. Take several samples to assure that an accurate
reading is obtained. Refer to
for the
proper carbon dioxide levels. If the measured
carbon dioxide level is within the listed values, no
adjustment is necessary. A carbon dioxide level
exceeding the listed range indicates incomplete
combustion due to inadequate air or excessive gas.
3. Check the manifold gas pressure by using the
manifold pressure port on the gas valve. Refer to
for the required manifold pressure
during low-fire operation. If it needs adjusting,
remove the cap covering the low-fire adjustment
screw on the gas valve. Refer to
for the adjustment screw location. Turn the screw
clockwise to increase the gas pressure or
counterclockwise to decrease the gas pressure.
N
No
otte
e:: Do not adjust the combustion air damper
while the furnace is operating at low-fire.
4. Check the carbon dioxide levels after each
adjustment.
5. Press the STOP key at the Human Interface Module
in the unit control panel to stop the system
operation.
Содержание IntelliPak 2 Series
Страница 217: ...RT SVX24Q EN 217 N No ot te es s...
Страница 218: ...218 RT SVX24Q EN N No ot te es s...
Страница 219: ...RT SVX24Q EN 219 N No ot te es s...