RT-SVX24Q-EN
39
Minimum Required Clearance
Figure 16.
Minimum required clearance
Filters
VFD
VFD
Heat
Rtn/Exh
Mtr
Rtn/Exh
VFD
Evp
(F)
Fltr
(F)
Sup
Mtr
Sup
VFD
Fltr
(R)
Evp
(R)
Heat
(L&R
Option
Option
As Req.
As Req.
As Req.
Std
Std
Std
Std
Blank Section
Final
Filter
Fnl
Fltr
As Req.
Fnl
Fltr
As Req.
Ctrl Box
(L&R)
Std
Outside
Air
Outside
Air
Exhaust
Condenser
Condenser
Exh
AH R
CBox
AH L
Cond L
Cond R
N
No
otte
e:: Unit drawing is representative only and may not accurately depict all models.
Table 18.
Minimum required clearance
Door Location
Availability
Unit Option Selection (Door Swing Ft. and In.)
Standard
VFD
Heat
Two-side
Access
Final
Filter
Energy
Recovery
90-
118
120-
162
Return/
Exhaust
Supply
Electric/
Hot
Water/
Steam
Reheat
90-
118
120-
162
Exhaust/Ret Motor
Std
2' 2"
2' 2"
*
*
*
*
*
*
*
Exhaust/Ret VFD
As Req.
*
*
2' 2"
*
*
*
*
*
*
ERW Fltr (L & R) (F)
Option
*
*
*
*
*
*
*
*
*
2' 2"
ERW Fltr(a) (L & R) (R)
Option
*
*
*
*
*
*
*
*
*
2' 2"
Filter (Front)
Std
2' 8"
2' 8"
*
*
*
*
*
*
*
Filter (Rear)
Option
*
*
*
*
*
*
2' 2"
2' 8"
*
Evap (Front)
Std
2' 2"
2' 2"
*
*
*
*
*
*
*
Evap (Rear)
Std
2' 8"
*
*
*
*
*
*
*
*
or Evap (Rear)
Option
*
*
*
*
*
2' 2
*
2' 2"
*
Supply Motor
Std
2' 8"
2' 8"
*
*
*
*
*
*
*
Supply VFD
As Req.
*
*
*
2' 2"
*
*
*
*
*
Heat (Left & Right)
As Req.
*
*
*
*
2' 2"
*
*
*
*
Final Filter (Front)
As Req.
*
*
*
*
*
*
*
*
2' 2"
Final Filter (Rear)
As Req.
*
*
*
*
*
*
*
*
2' 2"
Control Box (L & R)
Std
3' 2"
3' 2"
*
*
*
*
*
*
*
Minimum Required Clearance (Ft.)
AH_L
AH_R
Exh
Cond_L
Cond_R
Control
Box
8'
8'
8'
8'
8'
6'
Note:
See Unit Dimensions for Energy Recovery Wheel location.