RT-SVX24Q-EN
77
Table 31.
Electrical service sizing data — air-cooled and evaporative condensing (continued)
Fixed Capacity Compressors
Nom
Tons
AC/EC
Compressor
Nominal Voltage
Size
No per
Unit
460 V
575 V
380 V
RLA (ea.)
LRA (ea.)
RLA (ea.)
LRA (ea.)
RLA (ea.)
LRA (ea.)
130/140
315
2
44.7
260
35.8
210
44.6
260
374
2
52.1
320
41.1
235
52
320
150/162
374
4
52.1
320
41.1
235
52
320
Table 32.
Electrical service sizing data — eFlex™
Nom Tons
AC
Compressor
Nominal Voltage
Size
No per
Unit
460 V
575 V
380 V
RLA (ea.)
LRA (ea.)
RLA (ea.)
LRA (ea.)
RLA (ea.)
LRA (ea.)
90
170
(a)
1
42.9
N/A
35.6
N/A
53.5
N/A
184
4
28
160
21.7
135
34.3
160
105
170
1
42.9
N/A
35.6
N/A
53.5
N/A
184
3
28
160
21.7
135
34.3
160
250
1
34.1
215
27.3
175
34
215
120
170
1
42.9
N/A
35.6
N/A
53.5
N/A
184
2
28
160
21.7
135
34.3
160
250
1
34.1
215
27.3
175
34
215
315
1
44.7
260
35.8
210
44.6
260
130
170
1
42.9
N/A
35.6
N/A
53.5
N/A
184
2
28
160
21.7
135
34.3
160
315
1
44.7
260
35.8
210
44.6
260
374
1
52.1
320
41.1
235
52
320
150
170
1
42.9
N/A
35.6
N/A
53.5
N/A
184
1
28
160
21.7
135
34.3
160
250
1
34.1
215
27.3
175
34
215
374
2
52.1
320
41.1
235
52
320
(a)
Variable Speed Compressor
Содержание IntelliPak 2 Series
Страница 217: ...RT SVX24Q EN 217 N No ot te es s...
Страница 218: ...218 RT SVX24Q EN N No ot te es s...
Страница 219: ...RT SVX24Q EN 219 N No ot te es s...