104
RT-SVX24Q-EN
independent algorithms. A cluster will share a common
supply and return duct network.
Low Charge Protection
For each refrigeration circuit, the entering and leaving
evaporator temperatures are used to calculate
superheat. When the calculated superheat exceeds the
Evaporator Temperature Differential Setpoint minus 5°
F but not the Evaporator Temperature Differential
Setpoint, an information only, auto-reset, High
Superheat diagnostic is initiated. If the calculated
superheat exceeds the Evaporator Temperature
Differential Setpoint, a manual reset, low refrigerant
charge diagnostic is initiated and all compressors on
the circuit are locked out.
Hydronic Heat Sequence of Operation
Electrical circuitry for units with steam or hot water
heat is limited to the connections associated with the
modulating valve actuator and the freezestat.
Like the furnaces described earlier, steam and hot
water heat control systems are wired to ensure that
simultaneous heating and cooling do not occur. The
supply fan will cycle “On” and “Off” with each call for
heat during both an occupied and unoccupied period.
Whenever there is a call for heat, tth
he
e rre
ella
ay
y o
on
n tth
he
e h
he
ea
att
m
mo
od
du
ulle
e energizes. This allows a modulated voltage
signal to be sent to the “Wet” heat actuator. The value
of this signal regulates the flow of steam or hot water
through the coil by positioning the valve stem at some
point between fully closed (6 VDC) and fully open (8.5
VDC).
Freeze Protection
A freezestat is mounted inside the heat section of hot
water and steam heat units to prevent the “wet” heat
coil from freezing during the “Off” cycle.
If the temperature of the air leaving the heating coils
falls to 40°F, the freezesta’st normally open contacts
close, completing the heat fail circuit on the UCM.
When this occurs:
•
The supply fan is turned “Off”.
•
“Wet” heat actuator fully opens to allow hot water
or steam to pass through the heating coil and
prevent freeze-up.
•
A “Low Air Temperature Unit Trip” diagnostic is
displayed on the Human Interface LCD screen.
For heating control settings and time delay
specifications, refer to and
.
Startup the Unit
Use the following in conjunction with the
, to ensure that the unit is
properly installed and ready for operation. Be sure to
complete all of the procedures described in this section
before starting the unit for the first time.
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
☐
Turn the field supplied disconnect switch, located
upstream of the rooftop unit, to the “Off” position.
☐
Turn the 115 volt control circuit switch 1S2 to the
“Off” position. .
☐
Turn the 24 volt control circuit switch 1S3 to the
“Off” position. It is located in the secondary of the
1T2 - 1T5 transformers.
☐
Turn the “System” selection switch (at the Remote
Panel) to the “Off” position and the “Fan” selection
switch (if Applicable) to the “Auto” or “Off”
position.
☐
Check all electrical connections for tightness and
“point of termination” accuracy.
☐
Verify that the condenser airflow will be
unobstructed.
☐
Check the compressor crankcase oil level. Oil
should be visible in the compressor oil sight glass.
The oil level should be 1/2 to 3/4 high in the sight
glass with the compressor “Off”.
☐
Verify that all refrigerant service valves are back
seated on each circuit.
N
NO
OT
TIIC
CE
E
C
Co
om
mp
prre
esssso
orr D
Da
am
ma
ag
ge
e!!
E
Ex
xcce
essssiiv
ve
e lliiq
qu
uiid
d a
accccu
um
mu
ulla
attiio
on
n iin
n tth
he
e ssu
uccttiio
on
n lliin
ne
ess
cco
ou
ulld
d rre
essu
ulltt iin
n cco
om
mp
prre
esssso
orr d
da
am
ma
ag
ge
e..
D
Do
o n
no
ott a
allllo
ow
w lliiq
qu
uiid
d rre
effrriig
ge
erra
an
ntt tto
o e
en
ntte
err tth
he
e ssu
uccttiio
on
n
lliin
ne
e..
Do not start the unit in the cooling mode if the ambient
temperature is below the following minimum
recommended operating temperature:
Standard unit with or without HGBP — +45°F
N
No
otte
e:: See for minimum outside air temperature.
☐
Check the supply fan belts for proper tension and
the fan bearings for sufficient lubrication. If the
belts require adjustment, or if the bearings need
lubricating, refer to the Service/Maintenance
section of this manual for instructions.
☐
Inspect the interior of the unit for tools and debris.
Install all panels in preparation for starting the unit.