RT-SVX24Q-EN
Table 65.
Critical control parameters (continued)
Description
Suggested
Parameter
Economizer Settings
Region
1
Region
2
Region
3
Region
4
Region
5
Region
6
Region
7
Differential Comparative (Enthalpy
Changeover)
HOA > HRA
Notes:
1
.
See map in next figure for dry bulb changeover.
Examples:
- Minneapolis, Minnesota is in “Region 6" and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be
75°F.
- Charleston, South Carolina is in “Region 3" and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting
should be 65°F.
2
.
Using the Human Interface (HI), go to SETUP menu and input setting for parameters listed in the table above.
3
.
Use the Dry bulb changeover map to determine region of country based on unit site location.
4
.
Fixed speed compressor units 8°F deadband.
5
.
eFlex™ compressor units 4°F deadband.
Figure 143.
Dry bulb changeover map