RT-SVX24Q-EN
109
Table 47.
Service test guide for component operation — part II of II (continued)
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Sump Pump
Sump
Heater
Econo
Damper
Exhaust
Damper
VFD Output
1A
Closed
Closed
0%
Default
OFF
OFF
1B & 1C
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B & 2C
Closed
Closed
0%
Default
OFF
OFF
120 - 150 Ton — Air Cooled
1A
Closed
Closed
0%
Default
OFF
OFF
1B
Closed
Closed
0%
Default
OFF
OFF
1C & 1D
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
2B & 2C
Closed
Closed
0%
Default
OFF
OFF
2D
Closed
Closed
0%
Default
OFF
OFF
100, 118, 128, 140, 162 Ton — Evaporative Cooled
1A
Closed
Closed
0%
Default
OFF
OFF
2A
Closed
Closed
0%
Default
OFF
OFF
SUPPLY FAN
Closed
Closed
100%
Unocc
OFF
OFF
RETURN FAN
Closed
Closed
100%
Default
OFF
OFF
EXHAUST FA
N
Closed
Closed
100%
Default
OFF
OFF
GAS HEAT
(Full Capacity)
Closed
Closed
100%
Unocc
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
Full Modulating
Closed
Closed
100%
Unocc
OFF
OFF
ELECTRIC HEAT
Closed
Closed
100%
Unocc
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
Stage 3
Closed
Closed
100%
Unocc
OFF
OFF
HYDRONIC HEAT
Closed
Closed
100%
Default
OFF
OFF
OUTSIDE AIR
DAMPERS
Closed
Closed
100%
Default
OFF
OFF
EXHAUST
DAMPERS
Closed
Closed
100%
Default
OFF
OFF
EVAP COND
Sump Pump
Closed
Closed
100%
Default
ON
OFF
Sump Heater
Closed
Closed
100%
Default
OFF
ON
Service Testing for Evaporative Condenser
Components
From the Compressor and Condenser Service Menu
screens — Head Pressure Control: AUTO or Head
Pressure Control: MANUAL.
Select Head Pressure Control: MANUAL
N
No
otte
e:: All outputs, Sump Control, Fan Stage Control
and Fan Speed Control (per circuit where
specified), will be available for ON/OFF, OPEN/
CLOSED, 0–100% manual settings considering
the stipulations in the table below:
Table 48.
Service test guide component operation—evaporative condenser
Component Being Tested
Requirements (ON)
Requirements (OFF)
Compressors
Sump minimum level switch must be closed for a minimum of five minutes
No Requirements
Sump Pump
Sump minimum level switch must be closed for a minimum of five minutes
No Requirements
Condenser Fans
No Requirements
No Requirements
Fill Valve Relay
No Requirements
No Requirements
Drain Valve Actuator
No Requirements
No Requirements