79
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-14
[For special adjustment]
10.0 to 200.0
0.1
100.0
%
Armature current detection DCCT selection setting
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-15
Armature current detection DCCT
selection
0: Auto
1: P-side DCCT
2: N-side DCCT
- 0
-
Armature current detection DCCT selection (E-15):
In this parameter, set the DCCT to detect the armature current. When the armature current detection DCCT
selection is set to auto (E-15 = 0), this function selects a DCCT among DCCTs on the P side and N side
whichever its deviation from the armature current command is smaller.
Output voltage upon rated speed
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-16
Output voltage upon rated speed
(200 V class) 70 to 230
1
220
V
(400V class) 140 to 460
1
440
V
Output voltage upon rated speed (E-16):
In this parameter, set the voltage to be output upon the rated speed viewing the output voltage (Vout) on the
console panel (SET66-Z). This setting is used as the reference voltage for the voltage corresponding to the
speed that is used for the PG error protection (PEr) detection.
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
E-17 to 18 [No function]
*1
- -
-
-
*1: There is no function to be set.