101
JOG Proportion Gain Selection
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
i-13
JOG proportion gain selection
0: Speed control proportion gain (1) (7.ASrP)
to system inertia moment (1) (9.ASrJ)
1: Speed control proportion gain (2) (i-10)
to system inertia moment (2) (i-12)
2: [For special adjustment]
*1
1 15
-
*1: Provided for special adjustment. Usually do not set this item.
JOG proportion gain selection (i-13):
Set proportion gain, time constant, and inertia moment used for JOG operation.
- For speed control proportion gain (1) (7.ASrP) to system inertia moment (1) (i-13=0)
Setting values of the Speed control proportion gain(1) (7.ASrP), Speed control integral time constant(1)
(8.ASrI), and System inertia moment(1) (9.ASrJ) are used.
- For speed control proportion gain (2) (i-10) to system inertia moment (2) (i-12) (i-13=1)
Setting values of speed control proportion gain (2) (i-10), speed control integral constant (2) (i-11), and
system inertia moment (i-12) are used in JOG.
Speed Control (ASR) Selection
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
i-14
ASR cancellation usage selection
oFF (Unused)
on (Used)
- on
-
i-15
ASR feed-forward usage selection
oFF (Unused)
on (Used)
- on
-
ASR cancellation usage selection (i-14), ASR feed-forward usage selection (i-15):
For VF66B (DC motor drive), the robust speed control (MFC control) is configured in combination with
cancellation and feed-forward using the disturbance observer.
These cancellation and feed-forward can be switched between used/unused through ASR cancellation usage
selection and ASR feed-forward usage selection (i-14=on/oFF, i-15=on/oFF).
If both ASR cancellation usage selection and ASR feed-forward usage selection are set to unused (i-14=oFF
and i-15=oFF), the function is equivalent to conventional PI control. For details, refer to "6.1. Basic Setting
Area" in Chapter 6 and "7.1. Basic Setting Area" in Chapter 7.
Variable Structure Proportion Gain Adjustment
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
i-16
Variable structure proportion gain start
speed
0.01 to 100.00
0.01
5.00
%
i-17
Variable structure proportion gain
minimum gain percentage
0 to 500
1
100
%