Selection of stop mode
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
b-01
Stop mode selection
0: Free stop
1: Deceleration stop
- 1
-
b-02
Stop speed
0 to 300
1
30
r/min
b-03 [No
function]
*1
-
-
-
-
b-04 [No
function]
*1
-
-
-
-
b-05
JOG stop mode selection
0: Free stop
1: Deceleration stop
- 0
-
b-06
JOG stop speed
0 to 300
1 30
r/min
*1: There is no function to be set.
Stop mode selection (b-01), JOG stop mode selection (b-05):
In the Stop mode selection (b-01) and the JOG stop mode selection (b-05), select a behavior when turning off
an operation or jog command. When the Operation mode selection (i-07) is not "0" (speed control mode), free
stop always occurs regardless of the settings of (b-01) and (b-05).
Stop speed (b-02), JOG stop speed (b-06):
In the stop speed (b-02) and JOG stop speed (b-06), set speeds for stopping an operation or JOG operation.
Free stop
Deceleration stop
Turning off an operation or JOG
command will cause VF66B (DC motor
drive) to stop voltage output.
VF66B (DC motor drive) gradually
decelerates according to the deceleration
time until it reaches the settings of the Stop
speed (b-02) and the JOG stop speed
(b-06), and then it stops voltage output.
Operation/JOG
command
Motor speed
Output
current
Free run
Operation/JOG
command
Motor speed
Output
current
b-02/b-06
Caution
[About free run]
Note that a DC motor generates a voltage proportional to the speed even in a free run state due to the field
current. When you want to shut down the output voltage immediately after turning off the operation in a
case where the power constant area is used, insert an output MC (electromagnetic contactor) between the
motor and VF66B (DC motor drive) and operate this MC through the 52MA relay of VF66B (DC motor
drive).