112
- Transferring parameter data to external console panel [SET66EX-Z] (S-00=101):
The following steps show how to transfer parameter data to the VF66B (DC motor drive) unit and the
external console panel [SET66EX-Z].
Connect the VF66B (DC motor drive) unit to the optional external console panel [SET66EX-Z].
Press the [MONI/FNC] key to enter the FNC (function selection) mode (LED-FNC is lit).
Select "S-00" using [
↑
][
↓
] keys ("S" starts flashing). Confirm it with the [SET] key.
Shift the target digit to the right using the [JOG/
→
] key, edit the number with [
↑
][
↓
] keys to
enter "1040".
"S-00" is displayed again. Confirm it with the [SET] key.
Edit the number with [JOG/
→
][
↑
][
↓
] keys to enter "101", and confirm it with the [SET] key.
"VtoS" and "SurE" flash alternately.
Subsequently confirm it with the [SET] key.
*If communication with the external console panel [SET66EX-Z] is disabled, there is no response.
"VtoS" is displayed. Data is transferred from the VF66B (DC motor drive) unit to the external
console panel [SET66EX-Z].
"End" is displayed when the transfer is successfully completed.
Mode is displayed. After a few seconds the display returns to the monitor item.
* If normal communication fails during the data transfer, it is aborted with mode displayed, or
flashes for 10 seconds and then the transfer is aborted.
↓
To resume the transfer, wait until mode is displayed after interruption and the display returns to the monitor
item. Follow the same procedure from the beginning.
* When connecting the external console panel [SET66EX-Z] to the VF66B (DC motor drive) unit, the console panel
[SET66-Z] located on the VF66B (DC motor drive) unit becomes unavailable.
External console panel
[SET66EX-Z]
VF66B (DC motor drive) unit
VF66B
・ ・ ・
・・・
・ ・ ・
・・・