49
Table: Minimum values of setting range of A-02
VF66B
(DC motor drive)
model
Minimum value of
setting range of A-02
VF66B
(DC motor drive)
model
Minimum value of
setting range of A-02
2R222 0.75 2R244 0.75
3R722 1.10 3R744 1.10
5R522 1.50 5R544 1.50
7R522 2.20 7R544 2.20
1122 3.70 1144 3.70
1522 5.50 1544 5.50
2222 7.50 2244 7.50
3022 11.00 3044 11.00
3722 15.00 3744 15.00
4522 22.0 4544 22.0
5522 30.0 5544 30.0
7522 37.0 7544 37.0
9022
45.0
11044
45.0
15022 55.0 16044 55.0
18022 75.0 20044 75.0
25044 110.0
31544 160.0
40044 200.0
50044 250.0
60044 315.0
75044 400.0
100044 500.0
Rated motor capacity (A-02) to rated motor field current (A-07):
In each parameter from the rated motor capacity (A-02) to rated
motor field current (A-07), set each rating shown on the nameplate
or data sheet of the motor. Be sure to set them because they are
used during an operation. Set values shown on the motor's
nameplate as shown in the figure or motor's data sheet.
When the motor has two ratings for the rated voltage and rated
current, set values whichever are larger within the speed range to be
used to the rated motor armature voltage (A-03) and rated motor
armature current (A-04), respectively.
When you use the motor to the extent of the constant output (power
constant) area, set the base speed to the rated speed (A-05).
Motor's nameplate
Setting of number of PG-pulse
Console
panel
monitor
display
Contents
Setting range (selecting item)
Setting
resolution
Initialized
data
Unit
A-08
Number of PG-pulse
60 to 32767
1
600
P/R
Name-
plate
Set the values shown on the