131
Console LED display
Cause
Where to check and how to take
actions
Reference
(This is not a display for
protection.)
[Contents]
This is displayed only
when the emergency stop
A input contact is ON.
Console LED display
Cause
Where to check and how to take
actions
Reference
(This is not a display for
protection.)
[Contents]
This is displayed only
when the emergency stop
B input contact is ON.
Console LED display
Cause
Where to check and how to take
actions
Reference
1. It starts when the cooling fan of
VF66B (DC motor drive) failed.
Check the cooling fan of
VF66B (DC motor drive).
[Contents]
It starts when the cooling
fan of VF66B (DC motor
drive) failed.
(The operation is not
stopped for protection.)
Console LED display
Cause
Where to check and how to take
actions
Reference
1. The external failure signal was
input.
Check the input condition of
the external failure signal.
[Contents]
It starts when the field
loss signal or field
overcurrent signal of the
multifunction input was
input.
2. Multifunction input settings are
not correct.
Check multifunction input
settings (c-00 through c-17).
Chapter 6, 6.4 Area c
Chapter 7, 7.4 Area c
3. Field amplifier has detected the
field loss or field overcurrent.
Check the operation of the
field amplifier.