113
- Copying parameter data from external console panel [SET66EX-Z] to VF66B (DC motor drive) unit
(not copying data in area A)(S-00=102):
The following steps show how to transfer parameter data to the VF66B (DC motor drive) unit and the
external console panel [SET66EX-Z]. However, parameter data in area A is not copied.
* When changing unit models or motor models, apply the steps described below.
Connect the VF66B (DC motor drive) unit to the optional external console panel [SET66EX-Z].
Press the [MONI/FNC] key to enter the FNC (function selection) mode (LED-FNC is lit).
Select "S-00" using [
↑
][
↓
] keys ("S" starts flashing). Confirm it with the [SET] key.
Shift the target digit to the right using the [JOG/
→
] key, edit the number with [
↑
][
↓
] keys to
enter "1040".
Subsequently confirm it with the [SET] key. If entering any value other than "1040",
is
displayed.
"S-00" is displayed again. Confirm it with the [SET] key.
Edit the number with [JOG/
→
][
↑
][
↓
] keys to enter "102", and confirm it with the [SET] key.
"StoV1" and "SurE" flash alternately.
Subsequently confirm it with the [SET] key.
* If communication with the external console panel [SET66EX-Z] is disabled, there is no
response.
"StoV1" is displayed. Data is transferred from the external console panel [SET66EX-Z] to the
VF66B (DC motor drive) unit.
"End" is displayed when the transfer is successfully completed.
Power-on operation automatically starts after five seconds.
* If normal communication fails during the data transfer, it is aborted with mode displayed, or
flashes for 10 seconds and then the transfer is aborted.
⇒
To resume the transfer, follow the same procedure from
the beginning again after mode is displayed.
* If software version numbers stored in the VF66B (DC motor drive) unit and the external console panel
[SET66EX-Z] are different when confirming with the [SET] key after "StoV1" and "SurE" flashing alternately,
starts flashing. If selecting the [STOP/RESET] key with
displayed, copy is
interrupted. If selecting the [SET] key, copy is continued.
* When connecting the external console panel [SET66EX-Z] to the VF66B (DC motor drive) unit, the console panel
[SET66-Z] located on the VF66B (DC motor drive) unit becomes unavailable.
External console panel
[SET66EX-Z]
VF66B (DC motor drive) unit
VF66B
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・