E6581531
E-4
5
1) Increasing torque automatically according to the load
Set the automatic torque boost
CW
=
(automatic torque boost+auto-tuning 1)
Automatic torque boost
CW
=
detects load current in all speed ranges and automatically adjusts voltage output
from inverter. This gives steady torque for stable runs.
Note 1: The same characteristic can be obtained by setting the V/f control mode selection parameter
RV
to
(automatic torque boost) and
H
(auto-tuning 1) to
.
⇒
Refer to Section 6.19.
Note 2: Setting
CW
to
automatically programs
RV
to
.
Note 3: If stable operation cannot be achieved with this setting, set the parameters
XN
(base frequency),
XNX
(base-frequency voltage),
H
(rated capacity of motor),
H
(rated current of motor) and
H
(rated number of revolutions of motor) as specified on the motor nameplate, and then set
H
to
and
CW
to
again.
2) When using vector control (increasing starting torque and high-precision operations)
Set the automatic torque boost
CW
=
(sensorless vector auto-tuning 1)
Setting automatic torque boost
CW
=
(Sensorless vector auto-tuning 1) provides high starting torque
bringing out the maximum in motor characteristics from the low-speed range. This suppresses changes in motor
speed caused by fluctuations in load to provide high precision operation. This setting is most suitable for transfer
and lifting systems that are operated in speed control mode.
Note 1: The same characteristic can be obtained by setting the V/f control mode selection parameter
RV
to
(Sensorless vector control) and
H
(Auto-tuning 1) to
.
⇒
Refer to Section 6.19.
Note 2: Setting
CW
to
automatically programs
RV
to
.
Note 3: If stable operation cannot be achieved with this setting, set the parameters
XN
(base frequency),
XNX
(base-frequency voltage),
H
(rated capacity of motor),
H
(rated current of motor) and
H
(rated number of revolutions of motor) as specified on the motor nameplate, and then set
H
to
and
CW
to
again.
CW
(automatic torque boost) and
RV
(V/f control mode selection)
Automatic torque boost is the parameter for setting V/f control mode selection (
RV
) and auto-tuning 1 (
H
)
together. That is why all parameters related to change automatically when
CW
is changed.
Automatically programmed parameters
CW
RV
H
Disabled (Always
is displayed.)
–
Check the programmed
value of
RV
. (If
CW
is not
changed, it becomes
(V/f
constant).)
–
Automatic torque boost+auto-tuning 1
Automatic torque boost
: Executed (
after
execution)
Sensorless vector auto-tuning 1
Sensorless vector control
: Executed (
after
execution)
3) Increasing torque manually (V/f constant control)
The VF-PS1 inverter is set to this control mode by factory default.
This is the setting of constant torque characteristics that are suited for such things as conveyors. It can also be used
to manually increase starting torque.
To return to V/f constant control after changing the
CW
setting:
Set the V/f control mode selection parameter
RV
=
(constant torque characteristic).
⇒
Refer to Section 5.6.
Note: If you want to increase torque further, raise the setting value of manual torque boost
XD
.
How to set manual torque boost parameter
XD
⇒
Refer to Section 5.7.
If vector control cannot be programmed....
First read the precautions about vector control in 5.6, 10).
1) If the desired torque cannot be obtained
⇒
Refer to 6.19 selection 3.
2) If auto-tuning error “
GVP
” appears
⇒
Refer to 13.1 and 6.19 selection 3.