E6581531
F-50
6
6.26.9 Detection of output short circuit
H
: Selection of short circuit detection at starting
• Function
Detects a short-circuit on the output side of the inverter.
Title
Function
Adjustment range
Default setting
H
Selection of short circuit
detection at starting
:Each time (standard pulse)
:Only one time after power is turned on
:Each time (short pulse)
:Only one time after power is turn on (short pulse)
:Each time (Extremely shot-time pulse)
:Only one time after power is turn on (Extremely
shot-time pulse)
H
·················
,
,
: Standard —— detecting at starting
,
,
: A check is made once at the first start of operation after the power is turned on or the
inverter is reset.
Note: If the input voltage is rather high (480V as a guide) or the inverter is used to operate a high-speed motor, set
H
to
or
. Any other setting may cause the motor to malfunction, because a high-speed motor has a
very low impedance. If the inverter malfunctions for reasons of impedance even though
H
is set to
or
, then set
H
to
or
.
6.26.10 Overtorque trip
H
: Overtorque trip selection
H
: Overtorque detection level during power running
H
: Overtorque detection level during regenerative braking
H
: Overtorque detection time
H
: Overtorque detection hysteresis
• Function
Trips the inverter or issues an alarm if the total time for which torque is above the level set with
H
/
H
reaches the time set with
H
. Trip information is displayed as “
QV
.”
H
=
(No trip) ·············· No tripping (FL is not active).
H
=
(Tripping) ············ The inverter will trip (the failure signal FL will be activated) if a torque larger than
H
(during power running) or
H
(during regeneration) passes for a time
longer than the time set with
H
.
Title
Function
Adjustment range
Default setting
H
Overtorque trip selection
:No trip
:Trip
H
Overtorque detection level during power running
~
%
H
Overtorque detection level during regenerative braking
~
%
H
Overtorque detection time
~
sec.
H
Overtorque detection hysteresis
~
%
Note: Using the output terminal function selection parameter, the inverter can be set so that it outputs overtorque
detection signals regardless of the setting of
H
.
⇒
Refer to Section 7.2.2.
<Example of operation>
Output terminal function: 28 Overtorque detection
H
=
(No trip)
Ex.) When outputting overtorque detection signals through output terminal OUT1
Title Function
Adjustment
range
Example of
setting
H
Output terminal function selection 1(OUT1)
~