K-28
E6581531
11
[21] Communication function [3/7]
Sensorless vector/vector with sensor (
●
:Effective, -:Ineffective)
Default setting
Title
Communication
No.
Function Adjustment
range
Minimum
setting unit
(Panel/Communi
cation)
V[R
=
500V
-50Hz
V[R
=
575V
-60Hz
V[R
=
690V
-50Hz
Write
during
running
Vector
control
V/f
Constant
Reference
H
0800
Communication speed (2-wire RS485)
0:9600 bps
1:19200 bps
2:38400 bps
1/1
1 1 1
Enabled
●
/
●
●
6. 34. 1
H
0801
Parity (common to 2-wire RS485 and
4-wire RS485)
0:Non parity
1:Even parity,
2:Odd parity
1/1
1 1 1
Enabled
●
/
●
●
6. 34. 1
H
0802
Inverter number (common)
0~247
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0803
Communications time-out time (common
to 2-wire RS485 and 4-wire RS485)
0:OFF, 1~100 sec.
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0804
Communications time-out action
(common to 2-wire RS485 and 4-wire
RS485)
0~8 1/1
8 8 8
Enabled
●
/
●
●
6. 34. 1
H
0805
Send waiting time (2-wire RS485)
0.00:Default, 0.01~2.00 sec.
0.01/0.01
0.00
0.00
0.00
Enabled
●
/
●
●
6. 34. 1
H
0806
Master/slave setting for
inverter-to-inverter communications
(2-wire RS485)
0:Slave (issues a 0Hz command if something
goes wrong with the master)
1:Slave (continues operation if something goes
wrong with the master)
2:Slave (trips for emergency stop if something
goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5. -
6. -
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0807
Protocol selection (2-wire RS485)
0:TOSHIBA
1:MODBUS
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0808
Communication 1 time-out condition
selection
0:Disconnection detection
1:When communication mode enable
2:1+Driving operation
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0810
Frequency point selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
1/1
0 0 0
Enabled
●
/
●
●
6. 34. 1
H
0811 Point
1
setting
0-100%
1/1 0 0 0
Enabled *1
●
/
●
●
6. 34. 1
H
0812
Point 1 frequency
0.0~
HJ
Hz
0.1/0.01
0.0 0.0 0.0
Enabled *1
●
/
●
●
6. 34. 1
H
0813 Point
2
setting
0~100%
1/1 100 100 100
Enabled *1
●
/
●
●
6. 34. 1
H
0814
Point 2 frequency
0.0~
HJ
Hz
0.1/0.01
50.0
60.0
50.0
Enabled *1
●
/
●
●
6. 34. 1
*1: Effective when a command value is sent by communication.