E6581531
F-30
6
Title
Function
Adjustment range
Example of setting
H
Commercial power/inverter switching output selection
~
or
H
Commercial power/inverter switching frequency
~
WN
Hz
Power supply frequency etc.
H
Inverter-side switching waiting time
~
sec.
According to model
⇒
Refer to page K-41.
H
Commercial power-side switching waiting time
~
sec.
H
Commercial power switching frequency holding time
~
sec.
H
Input terminal function selection 7 (S3)
~
(Commercial power switching)
H
Output terminal function selection 1 (OUT1)
~
(Commercial power/inverter
switching output 1)
H
Output terminal function selection 2 (OUT2)
~
(Commercial power/inverter
switching output 2)
- Warning -
• When switching to commercial power, make sure that the direction in which the motor rotates when operated
on commercial power agrees with the forward direction when operated via the inverter.
• Do not select any option (
H
=
) of
H
(reverse rotation prohibition selection) that prohibits forward
rotation. Or it becomes impossible to switch to commercial power, because the motor cannot rotate in the
forward direction.