9.2.3 Caution as to peripheral devices
When installing a no-fuse circuit breaker or a fuse box on the primary side of the inverter, use UL-certified one.
The UL certification test on this inverter was conducted under the power supply short-circuit current* conditions
shown in Table 4 (*: current that flows in the event of a short-circuit in the power supply). Note that power supply
short-circuit currents vary depending on the capacity of the motor used.
Table 4 Power supply short-circuit current and maximum input voltage
Input voltage
(V)
Applicable motor
(kW)
Power supply short-circuit current (A)
1.5~90
Suitable for use on a circuit capable of delivering not more than 22,000 rms
symmetrical amperes in below, 600 volts maximum.
110,132
Suitable for use on a circuit capable of delivering not more than 28,000 rms
symmetrical amperes in below, 600 volts maximum.
160~315
Suitable for use on a circuit capable of delivering not more than 35,000 rms
symmetrical amperes in below, 600 volts maximum.
600
400~630
Suitable for use on a circuit capable of delivering not more than 42,000 rms
symmetrical amperes in below, 600 volts maximum.
Table 5
AIC, Fuse and Wire sizes
Applicable
motor
HP KW
Inverter model
UL
output current
(A) *1
AIC (A)
(Interrupting
capacity)
UL-fuse 600V class
and current
(A)
Input wire
sizes of
power circuit
*2
Output wire
sizes of
power circuit
*2
Earth
*2
3 2.2
VFPS1-5022PM
3.9
22000
Class J 15A max
AWG14
AWG14
AWG14
5 4
VFPS1-5040PM
6.1
22000
Class J 25A max
AWG14
AWG14
AWG14
7.5 5.5
VFPS1-5055PM
9.0
22000
Class J 30A max
AWG12
AWG14
AWG14
10 7.5
VFPS1-5075PM
11.0
22000
Class J 35A max
AWG10
AWG14
AWG12
15 11
VFPS1-6150PL
17.0
22000
Class J 35A max
AWG8
AWG8
AWG10
20 15
VFPS1-6185PL
22.0
22000
Class J 45A max
AWG8
AWG8
AWG10
25 18.5
VFPS1-6220PL
27.0
22000
Class J 60A max
AWG6
AWG6
AWG10
30 22
VFPS1-6300PL
32.0
22000
Class J 60A max
AWG4
AWG4
AWG10
40 30
VFPS1-6370PL
41.0
22000
Class J 90A max
AWG3
AWG3
AWG8
50 37
VFPS1-6450PL
52.0
22000
Class J 110A max
AWG2
AWG2
AWG8
60 45
VFPS1-6550PL
62.0
22000
Class J 125A max
AWG2
AWG2
AWG8
75 55
VFPS1-6750PL
77.0
22000
Class J 150A max
AWG1/0
AWG1/0
AWG6
100 75
VFPS1-6900PL
99.0
22000
Class J 200A max
AWG2/0
AWG2/0
AWG6
125 90
VFPS1-6110KPC
125
100000
Class J 200A max
AWG2/0
AWG2/0
AWG6
150 110
VFPS1-6132KPC
144
100000
Class J 200A max
AWG3/0
AWG3/0
AWG2
200 160
VFPS1-6200KPC
192
100000
Class J 300A max
250MCM
250MCM
AWG2
250 185
VFPS1-6250KPC
242
100000
Class J 400A max
2X250MCM
2X250MCM
AWG1
350 250
VFPS1-6315KPC
336
100000
Class J 500A max
2X350MCM
2X350MCM
AWG2/0
450 315
VFPS1-6400KPC 412
100000
Class J 2x300A max
3X300MCM 3X300MCM AWG3/0
500 400
VFPS1-6500KPC 528
100000
Class J 2x400A max 2X(2X300MCM) 4X300MCM
AWG4/0
700 500
VFPS1-6630KPC 672
100000
Class J 2x500A max 2X(2X400MCM) 4X400MCM
AWG4/0
*1: UL output current is different from unit rating output current.
*2: The cables used must be 75°C copper cables within 40°C ambient temperature.
9.2.4 Caution as to the protection of motors from overload
When using the inverter’s thermal protection function to protect the motor from overload, read the instruction
manual included with the inverter carefully and set parameters according to the specifications of the motor used.
When using the inverter to control the operation of multiple motors, install an overload relay for each individual
motor.